m. Place ground rod as close as possible and drive to a depth of
approximate 8 feet at a 450 angle.
n. Connect one end of the ground strap to ground terminal stud of
generator set and ensure terminal nut is tight.
o. Connect the other end of the
ground
strap
to
ground
rod
terminal screw and ensure it is tight.
WARNING
DO NOT INSTALL OR CHANGE THE LOAD CABLES WHILE
SET
IS
OPERATING.
THE
VOLTAGE
GENERATED BY THIS EQUIPMENT CAN CAUSE DEATH.
ARRANGE LEADS TO AVOID A SHORT OCCURRING IF CABLE
IS BUMPED OR PULLED.
TIE THE CABLE IN POSITION
WITH INSULATION MATERIAL IF NECESSARY.
p. Attach lead ends of power cable
to
load
terminal
board
requirement. (See Table 4 and Figure 23.)
TABLE 4.
CABLE CONNECTIONS.
WARNING
THE VOLTAGE GENERATED BY THIS EQUIPMENT CAN CAUSE
DEATH BY ELECTROCUTION. NEVER ATTEMPT TO MAKE A
VOLTAGE CHANGE AT THE TERMINAL STUDS OR PHASE
39